Menu
Vaccum Relief Valve
VRV 100
Pressure / vacuum relief valves or breather valves are special types of relief valves which are specifically designed for tank protection. The range includes pressure only, vacuum only and combined pressure / vacuum valves, all available with flanged outlets or vented to atmosphere Pressure / vacuum relief valves are used extensively on bulk storage tanks, including fixed roof tanks with floating covers, to minimize evaporation loss. The valves prevent the buildup of excessive pressure or vacuum which can unbalance the system or damage the storage vessel.
The range includes pressure only, vacuum only and combined Pressure/Vacuum Valves, all available with flanged outlets or vented to atmosphere. Pressure/Vacuum Relief Valves are used extensively on bulk storage tanks, including fixed roof tanks with floating covers, to minimize evaporation loss. Pressure/vacuum relief valves prevent emission losses until very close to the set pressure, and prevents air intake until very close to the set vacuum. The geometry of the valves has been developed in order to optimize overall performance in terms of high flow capacity, set pressure, sealing and re-sealing.
The Vacuum Relief Valve is an advanced design for vent to atmosphere applications. Utilizing the latest
technologies, this relief valve provides protection against negative or positive pressure, prevents air
intake, evaporative loss of product and helps contain odorous and potentially hazardous vapors.
The Vacuum relief valve is designed to be installed on pressurized tanks static or transportation
application. The vacuum relief valves prevent the unallowable entrance of air up to the adjusted set
pressure and offer reliable protection against vacuum.
Operation
Teleflo makes vacuum relief valves (VRV) in various metallic materials, with a wide
variety of elastomeric seat seals. There are several sizes available, as well as pressure
settings. The purchaser must exercise care to select the most desirable combination of
features for the intended service conditions.
Since the VRVs are frequently small in size, and are set at very low pressures, these
valves cannot withstand much abuse. Although the valve’s sole purpose is to
permit air from the atmosphere to be introduced into the tank when a negative
pressure (of a prescribed amount) occurs in the tank, it has been used wrongly on
occasions to ascertain if positive pressure exists in the tank. As an example, an operator
may push the stem down by stepping on it to see if there is pressure in the tank before
opening up the man way cover. A likely result of this is to damage the valve by bending the
stem, as well as releasing product that could harm the operator.
We would supply weather cover for VRV additionally if client requested. This part helps keep rain, cinders and other debris from accumulating in the inside of the valve
body, which when the valve opens, will then potentially drop into the tank. A weather
cover also serves as a deflector when there is flow out of the VRV to protect personnel near
the valve. the threads to facilitate getting a good
pressure-tight seal.
3. Do not use a large pipe wrench to install the
threaded valve. Care should be taken not to distort the valve body’s internal seat.
Remove the fasteners using suitable tools.
Note: All work on the valve should be
performed by a skilled mechanic with proper
tools.
Maintenance
The seal that makes the VRV bubble tight is the resilient seal. Do not try to lap the metal to metal seats between the stem and valve body.
The metallic seats on the stem and the valve body are carefully machined at an angle. Do
not attempt to reaching them. However, removing rust, solidified product, and other
debris by hand, or with emery paper is desirable.
The resilient seal of valves are almost always round shaped pressure seals.
Replacement pressure seals of whatever
material is required should be purchased
only from Teleflo.
Loosen and remove all nuts and washers.
Loosen and remove the cap.
Loosen the adjust screw and remove screw and nut.
Worn parts, gaskets, and seals should be replaced during reassembly.
Lift off the vacuum bonnet and cap.
The bonnet have a snug fit. Loosen the hex nuts that retain the bonnet in the body a few turns; this will allow the bonnet to be removed easily.
Remove the vacuum disc assemblies by firmly grasping the stems(spindle) and lifting up.
Loosen the adjust screw and remove screw and nut.
Worn parts, gaskets, and seals should be replaced during reassembly.
Lift off the vacuum bonnet and cap.
The bonnet have a snug fit. Loosen the hex nuts that retain the bonnet in the body a few turns; this will allow the bonnet to be removed easily.
Remove the vacuum disc assemblies by firmly grasping the stems(spindle) and lifting up.
VALVE TESTING PROCEDURE
Mount the valve on the test stand using proper tools with skilled person.
Test the vacuum test three times to verify proper operation. Record all test vacuum readings on the Shop Data Sheet.
With the valve mounted on the test stand,
slowly increase the vacuum pressure while
monitoring the air supply pressure flow rate.
For vacuum tests, the block valve is opened
sufficiently to allow a steady increase in
vacuum condition. To adjust the adjustment
screw as the setting is approached, continue
to open the valve.
The set (vacuum) will be the point at which
the test pressure (vacuum) does not increase with a corresponding increase in flow rate.
Normally, at this point, the test pressure
(vacuum) will fluctuate up and down as the
valve relieves, while the flow rate remains
steady. The set vacuum is the maximum
vacuum achieved during the test.
Repeat this test two more times to achieve a total of three measurements of set pressure
and vacuum.
The acceptable tolerance range for set (vacuum) is +/- 10%. All three test results
must fall within the specified tolerances for
the vacuum settings listed on the sales order.
Record the three set vacuum measurements
on the Shop Data Sheet